A motor nameplate gives the rated mechanical output in kW, while a contactor table lists motor ratings for specified voltages and utilization categories. Matching the two figures is only the first step: the correct contactor also depends on the motor’s rated current, starting method, operating frequency, and the manufacturer’s published AC-3 or AC-4 ratings.
This guide explains how to read the relevant ratings and apply them to a practical selection. The examples use published data from the KRIPAL UKC1 contactor range and UKH-100 overload relay range. Always confirm the latest product catalog and the exact model configuration before specifying equipment.

Motor kW is a useful first filter, but it is not a complete selection criterion. Two motors with the same rated output can have different full-load currents because of differences in efficiency and power factor. Starting method, switching frequency, load inertia, and the required electrical life can also affect the suitable contactor.
The kW value on a motor nameplate normally describes mechanical output at the shaft under the stated rated conditions. It does not directly state the current drawn from the supply. Use the nameplate current where available; if it is unavailable, estimate current only as a preliminary check using voltage, efficiency, and power factor, then confirm against the motor data.
A direct-on-line (DOL) start commonly produces an initial current several times higher than the motor’s full-load current; six to eight times is a useful rule of thumb, not a guaranteed value. The actual starting current and acceleration time depend on the motor design, supply conditions, and driven load. Select the contactor using its published motor-duty rating and the specified operating conditions, rather than sizing it from the peak starting current alone.
Starting frequency also affects electrical life. A contactor switching a motor a few times a day will generally experience less switching wear than one switching the same motor many times an hour. Check the manufacturer’s permitted operating frequency and electrical endurance for the relevant utilization category and load; do not infer service life from running hours alone.
Contactor tables may list conventional thermal current (Ith), rated operational current (Ie), and motor power ratings for particular voltages and utilization categories. These values describe different conditions and must not be treated as interchangeable. For a typical squirrel-cage motor that starts and switches off while running, start with the published AC-3 rating at the supply voltage, then check the duty, operating frequency, environment, and coordination requirements. Coil voltage and overload protection are separate selection decisions.
Conventional free-air thermal current (Ith) is a thermal rating under specified test and installation conditions. Rated operational current (Ie) is associated with a stated operational voltage, utilization category, and duty. They are not synonyms. Ith alone is not a suitable basis for choosing a motor contactor: compare the motor’s nameplate current with the contactor’s published AC-3 or AC-4 operational rating for the actual application.
AC-3 applies to squirrel-cage motors where the contactor closes to start the motor and opens after the motor has reached normal running speed. It is the common starting point for ordinary DOL motor duty, provided the manufacturer’s ratings and the actual switching frequency and load conditions are met. Learn more about performance curves in our contactors selection guide.
AC-4 applies to demanding motor operations such as inching, plugging, and certain reversing duties where the contactor may make or break at high current. These operations can cause substantially greater contact wear than ordinary AC-3 duty. Do not classify every reversing circuit automatically as AC-4: check the actual operating sequence and the manufacturer’s application guidance.
| Utilization Category | What the Contactor Does | Effect on Rated Current |
|---|---|---|
| AC-1 | Non-inductive or lightly inductive loads | Often higher than motor-duty ratings; check specific rating |
| AC-3 | Squirrel-cage motor, switched while running | Motor starting and normal stopping; use published AC-3 rating |
| AC-4 | Inching, plugging, and reversing | Demanding switching; use published AC-4 rating and endurance |
| AC-6b | Capacitor bank switching | Separate capacitor-duty rating; not directly comparable |
AC-6b is a separate utilization category for switching capacitor banks. Its ratings and selection criteria are not directly comparable with motor-duty current ratings. A contactor selected for AC-3 motor duty should not be assumed suitable for capacitor switching; use a contactor specifically rated for the intended capacitor-bank duty.
A contactor table must be read across the correct voltage column and utilization category. A kW rating is valid only under the conditions stated by the manufacturer. Check the associated operational current, not just the model name or the thermal-current figure, and confirm that the table refers to the exact product series and revision being specified.
A contactor table may list different motor power ratings for different operational voltages because the current and switching conditions differ. Select the column that covers the actual supply voltage, then compare the motor’s nameplate current with the relevant AC-3 or AC-4 rating. Do not assume that a higher voltage automatically makes every selection suitable; the utilization category and published ratings still govern.
Avoid using a generic percentage of the contactor frame rating as a pass/fail rule. Instead, check the motor nameplate current against the manufacturer’s rated operational current for the relevant voltage and duty, then review starting frequency, electrical life, ambient temperature, enclosure conditions, and coordination with short-circuit protection.
| Model | AC-3 Rating (220–240 V) | AC-3 Rating (380–440 V) | AC-3 Rating (500–550 V) | AC-3 Rating (690 V) | Ith (Thermal Current) |
|---|---|---|---|---|---|
| UKC1-100/3 | 30 kW / 105 A | 55 kW / 105 A | 55 kW / 85 A | 55 kW / 65 A | 150 A |
| UKC1-125/3 | 37 kW / 125 A | 60 kW / 120 A | 60 kW / 90 A | 60 kW / 70 A | 150 A |
| UKC1-150/3 | 45 kW / 150 A | 75 kW / 150 A | 90 kW / 140 A | 90 kW / 100 A | 200 A |
| UKC1-180/3 | 55 kW / 180 A | 90 kW / 180 A | 110 kW / 180 A | 110 kW / 120 A | 230 A |
| UKC1-220/3 | 75 kW / 250 A | 132 kW / 250 A | 132 kW / 200 A | 132 kW / 150 A | 260 A |
Consider a 15 kW, 400 V motor that starts four or five times per hour. Its actual full-load current must be taken from the nameplate or motor data; a value around 30 A may be used only as an illustrative estimate. A DOL starting current may be several times higher, but that peak alone does not determine the contactor frame size.
The UKC1 table excerpt shown here begins at the 100 A frame and lists UKC1-100/3 at 55 kW / 105 A for 380–440 V. That rating demonstrates the published capability of this frame; it does not prove that a 15 kW motor requires a 100 A contactor. To recommend a model, consult the full KRIPAL range and select a contactor whose AC-3 rating at the actual voltage covers the motor nameplate current and stated duty, with the required electrical life and coordination.
Therefore, this table excerpt alone is not enough to identify the most economical contactor for a 15 kW motor: smaller frames are not shown. Do not select an oversized frame simply because its kW rating is higher or because the motor has a starting-current peak. Use the complete current product catalog and actual duty data to confirm the smallest suitable model.
The KRIPAL UKC1 range includes three-pole and four-pole versions. Coil voltage and auxiliary-contact configuration depend on the exact model and ordering specification, so verify these details in the current product datasheet rather than assuming every frame has identical options. Additional auxiliary contact blocks may be available for compatible models. Explore the KRIPAL AC contactor range.
The motor’s rated output does not change, but the suitable contactor may change with the starting and stopping sequence. Key factors are the utilization category, motor current, switching frequency, and manufacturer’s electrical endurance data.
DOL starting applies full line voltage to the motor. For a typical squirrel-cage motor that starts and then switches off at normal running speed, AC-3 is usually the relevant utilization category. The contactor must still be selected from the published rating for the actual voltage and duty, not from peak starting current alone.
DOL starting can create a significant voltage dip or mechanical shock, depending on the motor, load, and supply. Check the motor manufacturer’s starting data and the installation’s supply limitations before deciding on the starting method.
Star-delta starting reduces starting current compared with DOL, but it requires a correctly coordinated set of three contactors and a motor with six accessible winding terminals that is suitable for delta operation at the supply voltage. For a common arrangement, the line-side main contactor is selected for the relevant line current, the star contactor is often sized around one-third of motor rated line current, and the delta contactor around 1/√3 (approximately 58%) of line current. These are conventional guide values; actual selection depends on the circuit arrangement and manufacturer tables.
For a complete selection, use the manufacturer’s star-delta combination tables and verify the main, star, and delta contactors against the actual wiring arrangement.
Reversing and inching can require AC-4 ratings when the operating sequence makes or breaks current under demanding conditions. Check the actual control sequence and manufacturer guidance; a contactor suitable for ordinary AC-3 duty may not have adequate AC-4 endurance.
| Duty | Selection Basis | Typical Arrangement |
|---|---|---|
| AC-3, direct-on-line | Published AC-3 operational current & motor rating at supply voltage | One contactor |
| AC-3, star-delta main | Use manufacturer’s star-delta table & circuit arrangement | Three contactors as a coordinated set |
| AC-4, reversing | Published AC-4 rating & electrical endurance for reversing/inching | Two interlocked contactors |
Electrical interlocking prevents both reversing contactors from being energized simultaneously; a compatible mechanical interlock can provide an additional safeguard. Confirm that the selected contactors are designed to accept the specified interlock and that the control circuit and protection scheme are appropriate for the application.
The overload relay protects the motor against sustained overload conditions; it does not replace short-circuit protection. Select the relay’s adjustable range to include the motor nameplate current, and coordinate it with the contactor and upstream protective device according to the manufacturer’s instructions and applicable standards.
Choose a setting range that includes the motor’s nameplate full-load current, then set the relay in accordance with motor data, relay instructions, installation arrangement, and applicable requirements. The correct setting is not determined simply by adding a fixed margin to measured running current. Ambient temperature, trip class, installation location, and whether the relay measures line or winding current can affect selection and setting.
| Adjustable Current Range | Phase-Loss-Sensitive Version | Standard Version |
|---|---|---|
| 34 to 50 A | UKK-100 50 | UKH-100 50 |
| 39 to 57 A | UKK-100 57 | UKH-100 57 |
| 43 to 65 A | UKK-100 65 | UKH-100 65 |
| 54 to 80 A | UKK-100 80 | UKH-100 80 |
| 65 to 100 A | UKK-100 100 | UKH-100 100 |
| 85 to 125 A | UKK-100 125 | UKH-100 125 |
For illustration, a 30 kW, 400 V motor might have a nameplate current near 55 A, but the actual value varies by motor efficiency, power factor, and design. A 54–80 A relay range may encompass a 55 A nameplate current, subject to confirmation of the exact relay range, installation arrangement, trip class, and manufacturer’s instructions. Do not set the relay above the motor’s permissible protection setting merely to avoid nuisance trips.
The published UKH-100 range covers several adjustable current bands within the series’ stated overall range. Confirm the exact suffix and current band against the current KRIPAL datasheet. Compare the phase-loss-sensitive and standard versions using their published operating characteristics. Explore our thermal overload relay range.

Phase-loss sensitivity varies by relay design. A phase-loss-sensitive model is intended to improve protection under specified phase-loss or phase-imbalance conditions, but its response depends on the product’s construction and operating characteristics. Compare the relevant UKH/K model datasheets and select the version required by the application.
A packaged motor starter can simplify procurement and assembly by combining switching and overload protection, often with push buttons and an enclosure. It is suitable when the starter’s motor rating, duty, protection, and enclosure match the installation. It is not automatically preferable to separate components in every application.
A magnetic starter commonly combines a contactor and overload relay, and some packaged models also include push buttons and an enclosure. Check the exact product construction: not every starter includes the same enclosure, controls, or protective functions. The assembly’s enclosure rating applies only under the manufacturer’s specified installation conditions.
Read starter ratings at the actual supply voltage and confirm that the model is intended for the required starting method. The table below gives published power ratings as a selection aid, but motor nameplate current, starting duty, overload adjustment, and starter configuration must also be checked.
| Model | Motor Rating (200–220 V) | Motor Rating (380–440 V) | Motor Rating (500–550 V) | AC-1 Thermal Current |
|---|---|---|---|---|
| UKQ-9MB | 2.5 kW | 4 kW | 4 kW | 25 A |
| UKQ-12MB | 3.5 kW | 5.5 kW | 7.5 kW | 25 A |
| UKQ-18MB | 4.5 kW | 7.5 kW | 7.5 kW | 40 A |
| UKQ-22MB | 5.5 kW | 11 kW | 15 kW | 40 A |
| UKQ-32MB | 7.5 kW | 15 kW | 18.5 kW | 50 A |
| UKQ-40MB | 11 kW | 18.5 kW | 22 kW | 60 A |
| UKQ-50B | 15 kW | 22 kW | 30 kW | 80 A |
| UKQ-65B | 18.5 kW | 30 kW | 33 kW | 100 A |
A 22 kW motor at 400 V may fall within the published 22 kW rating shown for the UKQ-50B, but this is only a preliminary check. Confirm the motor nameplate current, the starter’s rated operating conditions, overload range, and starting duty. High-inertia loads may require a different trip class or starting arrangement.
The UKQ-85B is listed as a DOL magnetic starter with a metal enclosure and IP44 protection. Verify the current catalog for its exact voltage, motor power, and current ratings. Consider weather exposure, UV, temperature, corrosion, and installation instructions. View the KRIPAL magnetic starter range.
Where the motor is inside a machine and control gear is located in a remote panel, separate components may be more practical. A packaged starter suits local motor control when ratings, enclosure, and controls match the application. Panel builders should decide based on layout, wiring, maintenance access, environmental conditions, and required protection.
Common sizing errors usually arise from comparing the wrong rating or overlooking actual operating conditions. Before ordering, check each item against the motor nameplate and current technical data:
kW-Only Selection Error
Confusing Ith with AC-3
AC-3 Used for AC-4 Duty
Ignoring Temperature Limits
Wrong Overload Range
Coil vs Main Voltage Mix-up
Motor kW narrows the options, but final selection depends on motor nameplate current, supply voltage, utilization category, starting method, and operating frequency. Check the manufacturer’s AC-3 or AC-4 rating for the actual duty, then confirm electrical endurance, environmental conditions, overload protection, and short-circuit coordination. Do not rely on generic oversizing percentages or peak starting current alone.
Before requesting a quotation, record the motor’s rated kW and nameplate current, supply voltage and frequency, starting method, starts per hour, load characteristics, control-coil voltage, and enclosure or ambient requirements. With these details, KRIPAL can help verify a suitable contactor, compatible overload relay, or packaged starter against relevant product data.
For project-specific selection, confirm model suffixes, current and power ratings, coil options, overload ranges, and starter specifications against the latest KRIPAL datasheet. Final selection must follow the manufacturer’s instructions and applicable installation standards.
No. Motor kW indicates shaft mechanical output. You must compare the motor’s actual full-load nameplate current with the contactor’s rated operational current (Ie) for the specific supply voltage and utilization category (AC-3 or AC-4).
AC-3 applies to standard squirrel-cage motors that start and switch off while running at full speed. AC-4 covers demanding switching operations such as inching, plugging, and rapid reversing, which cause severe contact wear.
No. Conventional free-air thermal current (Ith) represents resistive load capacity (AC-1). Motor switching involves inductive inrush currents, so you must always use the published AC-3 or AC-4 operational current ratings.
Choose a thermal overload relay whose adjustable current setting range encompasses the motor’s nameplate full-load current (FLC), and set the dial directly to the FLC according to the manufacturer’s instructions.