| Parameter | UKM5-800C | UKM5-800S | UKM5-800H | UKM5-800U |
| Frame Rated Current Inm(A) | 800 | 800 | 800 | 800 |
| Rated current(A) | 630,700,800 | 630,700,800 | 630,700,800 | 630,700,800 |
| Poles | 3, 4 | 3, 4 | 3, 4 | 3, 4 |
| Rated insulation voltage Ui(V) | AC690 | AC690 | AC690 | AC690 |
| Arcing distance(mm) | ≤50(0*) | ≤50(0*) | ≤50(0*) | ≤50(0*) |
| Rated ultimate/
Service short-circuit breaking capacity (KA) |
AC690V: 10/10 AC400V: 45/45 AC230V: 85/85 | AC690V: 15/15 AC400V: 70/70 AC230V: 100/100 | AC690V: 20/15 AC400V: 100/100 AC230V: 150/100 | AC690V: 35/35 AC400V: 125/125 AC230V: 200/200 |
| Operation performance (times) | ON: 500
OFF: 2500 |
ON: 500
OFF: 2500 |
ON: 500
OFF: 2500 |
ON: 500
OFF: 2500 |
| Rated operation frequency(per hour) | 20 | 20 | 20 | 20 |